BEHATEST Capacitive High Voltage Detectors
Model: 90212-90226
Introduction:
● This family of Capacitive High Voltage Detectors have been designed to meet the latest IEC standards.
● Our 902xx Series are self starting and automatically activated when the High Voltage is applied to the contact electrode.
● They can also be manually armed before use by depressing the "TEST/ARMING" button.
● These detectors are intended for use on sinusoidal (50 or 60Hz) High Voltage Systems.
● Models are available to cover systems voltage from 11kV to 132kV.
● Our Detectors are utilized to determine if a system is live or not, so that it maybe safely earthed/grounded.
● All our models are designed for outdoor, but can be utilized indoor and in all weather condition.
● This family of capacitive High Voltage Detectors are housed in a rugged, reinforced nylon moulded casing and are shock drop and vibration resistant.
● Non-standard threshold voltages can be customized to suit applications requirements
● The 902xx Series have a low battery detection which inhibit manual arming when the battery is too low.
● The Nylon case is easy to clean and maintain and the 902xx Series are supplied with the cleaning kit.
● A visual indication shows when the 902xx Series is armed. When armed, the Green Leds flashes about twice per second.
● When High Voltage is detected, the Red leds flashes about twice per second and the buzzer also buzz intermittently.
Features:
● Excellent Shock Resistance.
● Rugged Nylon moulding.
● Auto-ON(when Voltage Detected).
● Excellent Drop Resistance.
● Good Vibration Resistance.
● Loud Sound Alarm Indication.
● Built-in Proving and self-test circuit.
● High Bright Color Coded LEDs.
● Works from normal 9V battery.
● Interchangeable Contact Electrode.
● Use in All Whether Conditions.
● Compatible with all link sticks.
● Lightweight, Robust & Compact.
● Models available from 11kV to 132kV.
● Suitable for indoor and outdoor use.
● Self(Auto-ON) or Manual Arming.
● Easy access to batteries.
● Customized threshold on demand.
● Auto-Off(if no voltage detected).
● Meets IEC 61243-1/IEC 60068-2-2/IEC 60068-2-6/IEC 60068-2-32/IEC 60529
Models and Comparison Table:
Model
|
90212
|
90213
|
90214
|
90215
|
90216
|
90217
|
90218
|
90219
|
System Voltage
|
4/15 kV
|
11kV
|
33kV
|
66kV
|
132kV
|
11/33kV
|
44/132kV
|
66/132kV
|
Threshold Set within Range
|
1.9-2.1kV
|
1.65-4.4kV
|
4.95-13.2kV
|
11-13kV
|
11-13kV
|
3.3-4.95kV
|
11-13kV
|
11-13kV
|
Threshold
|
2.0kV
|
3.02kV
|
9.07kV
|
12kV
|
12kV
|
4.12kV
|
12kV
|
12kV
|
Response Time
|
<1 Sec
|
|||||||
Auto-OFF
|
3 Min
|
|||||||
Bridging Protection
|
YES
|
|||||||
Spark Protection
|
YES
|
|||||||
Battery Low
|
<7V
|
|||||||
Battery Current
|
<30mA
|
|||||||
Green=Armed
|
YES
|
|||||||
Red=V Detected
|
YES
|
|||||||
Test / Arming Button
|
YES
|
Model
|
90220
|
90221
|
90222
|
90223
|
90224
|
90225
|
90226
|
System Voltage
|
6.6/132kV
|
11/132kV
|
11/44kV
|
33/132kV
|
44kV
|
KV/User Defined
|
12/36 kV
|
Threshold Set within Range
|
2-3kV
|
4.4-6.6kV
|
4.4-5kV
|
11-13kV
|
6.6-17.6kV
|
X-X kV
|
5-6kV
|
Threshold
|
2.5kV
|
5kV
|
4.75kV
|
12kV
|
12kV
|
User’s Spec.
|
5.4kV
|
Response Time
|
<1 Sec
|
||||||
Auto-OFF
|
3 Min
|
||||||
Bridging Protection
|
YES
|
||||||
Spark Protection
|
YES
|
||||||
Battery Low
|
<7V
|
||||||
Battery Current
|
<30mA
|
||||||
Green=Armed
|
YES
|
||||||
Red=V Detected
|
YES
|
||||||
Test / Arming Button
|
YES
|
Please note the internal proofing circuit does not test the contact electrode and the protection devices.
Scope of Supply:
1pc 902xx high voltage detector
1pc carrying case
3pc metal hook (for hooking wires and cables)
1pc bottle of anti-static cleaning fluid and cleaning cloth
1pc 9V battery
Optional Hot Stick:
1 pc hot stick (1.2m)
1 pc Hot sticks kit 9660B(6.6m)
1 pc Hot sticks kit 9770B