9073 UNITEST TELARIS 0100 plus

Model:9073
Price:0US$

UNITEST TELARIS 0100 plus 9073
Multifunction Electrical Safety Test
Electrical installation tester
 Details



UNITEST TELARIS 0100 plus

Model: 9073

Key Functions
• Loop resistance measurement up to 265 V
• Line resistance measurement up to 440 V
• Prospective short circuit current measurement
• RCD measurements (contact voltage, trip time, trip current - ramp method)
• Low Ohm measurement
• Insulation measurement with 100, 250 500 V
• Voltage and frequency measurement
• Rotary field test

General Information
• Integrated memory for approx. 500 measurement values
• Standard, built-in IR RS-232 interface for transferring measurement data to the PC
• UNITEST software for recording test results is available as option
• Integrated socket test with contact electrode to ena-ble the user to quickly establish incorrectly installed sockets and/or protective conductor failures
• Clear and large LCD providing the user with an optimum visual indication of both test values and limits
• Auto power off

Special Features
• Measurement of loop resistance and prospective short circuit current measurement without trippingthe RCD
• Direct Printing of Protocols via an external Printer

Technical data:
Display
LCD, 3 1/2-digit, 1999 Digits
Measurement Ranges/Resolution
 
Voltage
1...440 V/1V AC/DC
Frequency
10...99,9 Hz/0,1 Hz
Loop Impedance
0,15…19,99./199,9/1999 Ω
0,01/0,1/1 Ω
Prospective Short Circuit Current
0,10 A...1,7 kA/0,01A...0,1 kA
 
 
Input Voltage Range
195...264 V 50/60 Hz
Test Current
approx.4,6 A (at 230 V)
Line Resistance
0,15…19,99./199,9/1999 Ω
0,01/0,1/1 Ω
Prospective Short Circuit Current
0,10 A...2,7 kA/0,01A...0,1 kA
Input Voltage Range
195...440 V 50/60 Hz
Test Current
approx.4,6 A (at 230 V)
Loop Resistance(without tripping the RCD)
0,5...19,99./199,9/1999 Ω
0,01/0,1/1Ω
Prospective Short Circuit Current
0,50 A...0,5 kA/0,01A...0,1kA
Input Voltage Range
195...264 V 50/60 Hz
Test Current
approx. 5 mA (at 230 V)
Insulation Resistance
0,05...19,99/199,9 MΩ
0,01/ 0,1 MΩ
Test Voltage
100, 250, 500 V DC
Low Ohm Measurement
0,05...19,99/199,9/1999 Ω
0,01/0,1/1 Ω
Test Current
> 200 mA DC
RCD-Test Nominal
10, 30, 100, 300, 500mA
currents
0,5 x 30mA, 5 x 30mA
selective:
100, 300, 500mA
Functions
trip time,
Tripping current test with ramp method
Contact Voltage
1...63 V
Earth Resistance
10…1999 Ω/19,99 kΩ
1 Ω/0,01 kΩ
Tripping Time
1...500 ms/1 ms
Tripping Current
40...140% of I∆N (in 10% steps)
Rotary Field Test
 
nput Voltage Range
100...440 V 50/60 H
 
 
Data memory
approx. 500 values
Interface
IR-RS-232
Safety complying with
IEC61010, EN61010,
DIN VDE 0411/
IEC61557, EN61557,
DIN VDE 0413
Measurement category
CAT III/440V
Pollution Degree
2
Protection Degree
IP 40
Power Supply
6 x 1,5 V, IEC LR6
Dimensions
235 x 105 x 70 mm
Weight
approx. 650 g
 
 
Scope of Supply:
1 pc UNITEST TELARIS 0100 plus
1 pc Test lead with Schuko plug system
3 pc Test lead with safety plug
3 pc Crocodile clamps
3 pc Test Probes1 pc Protective Holster
1 pc Carrying Case
6 pc Batteries 1.5V, IEC LR6
1 pc Instruction Manual





 

 
 

  |About us | Contact | Copyright © 2011 Shanghai Beha Electronics Co.,Ltd |