Determination of the Phase Presence
|
|
Nominal Voltage for Phase Presence Indication (the voltage
required for the neon lamps L1, L2, L3 to lit up)
|
From 100Vac to 450Vac.
|
Frequency Range
|
From 10Hz to 400Hz
|
Determination of the Phases Rotary Field Direction:
|
|
Direction (the voltage required to have the direction LEDs
L1-L2-L3 or L2-L1-L3 to indicates)
|
From 100 to 450Vac
|
Frequency Range
|
From 2Hz to 400Hz
|
Protection
|
|
Over Load
|
550V(between all terminals)
|
Over Voltage
|
Class III - 450V towards
ground
|
Earth Leakage
|
|
Current Settings
|
999mAac / 50Hz-60Hz
|
Current Selection
|
Knob
|
Phase Start Selection(*)
|
0° and 180°
|
Over-Temperature Protection(*)
|
Yes
|
Phase Polarity Trip Indicator(*)
|
Yes
|
Operating Voltage ( L-E )
(*)Referenced to Earth
|
110Vac to 317Vac
|
Timer Resolution
|
1ms(Max Time = 99.99s)
|
Timer Accuracy
|
1ms ± 4ms
|
Current Accuracy
|
±3% ± 4mA
|
Current Resolution
|
1mA
|
Voltmeter Accuracy (50Hz)
|
50-350 Vac = ± 3%±2V
350-550Vac = ± 7%±3V
|
Voltmeter Resolution
|
1V
|
Maximum Current Specified at 317Vac / 50Hz Batteries
|
1.5V "C" x 8
Bat OK Led = Vbat >9V
|
Dimensions
|
330(L) x 260(W) x 160(D)mm
|
Weight
|
3.85 kg(battery included)
|
Operating temperature Range
|
-15°C to +55°C
|
Storage Temperature
|
-20°C to +70°C
|