Current Settings
|
3mA, 5mA, 10mA, 15mA, 20mA, 30mA, 50mA, 100mA, 150mA, 250mA, 300mA, 500mA
|
Current Selection
|
Rotary switch selector
|
Phase Angle Setting
|
0° and 180° selectable
|
Operating Voltage (L-E)
|
Verson A : 240V/AC, Version B : 230V/AC,
|
(50Hz or 60Hz)
|
Version C : 220V/AC, Version D : 110V/AC
|
Voltmeter (L-E)
|
20V - 280V (50Hz or 60Hz)
|
Over-Temperature Protection
|
Yes (3 sensors)
|
Wiring Correctness Indication
|
Yes (LCDs)
|
Trip Indicator
|
Yes (LCD)
|
Phase Polarity Trip Indicator
|
Yes (LCD) Referenced to Earth
|
Timer Resolution
|
1ms (max time : 19.99s)
|
Timer Accuracy
|
± 2ms
|
Current Accuracy
|
± 5% ±1mA
|
Voltmeter Resolution
|
1V/AC
|
Voltmeter Accuracy
|
± 2% ± 1V/AC
|
Operating Temperature
|
-5 ℃ to 45 ℃
|
Storage Temperature
|
-10 ℃ to 85 ℃
|
Safety complying with
|
IEC/EN 61010-1
|
Measurement category
|
CAT III 300V
|
Power supply
|
6 x 1.5V, IEC LR6
|
Dimensions
|
205 x 90 x 55 mm
|
Weight
|
Approx. 530g (battery included)
|